CHAPTER 6 DIGITAL LINES
RPC-2300 Page 17
Figure 6-2 Inductive load protection
a 1 is written to the high cur rent por t, the output is
switched on and goes low.
The output driver chip, U 20, can be replaced with a DIP
shunt jumper so it is like the other lines at J3.
NOTE: Outputs at the high current lines are not
compatible with TT L logic levels and should
not be used to drive other logic devices.
Each of the high current outputs can sink 100 ma at 50V.
WARNING:
External supplies using the high current outputs must
be tied to J3, pin 26 and NOT the power connector.
Failure to do so can produce a ground loop and
cause erratic operation.
The thermal time constant of U20 is very short, so the
number of outputs that are on at any one time should
include those that overlap even for a few milliseconds.
Incandescent lamps have a "cold" current of 11 times its
operating current. Lamps requiring more than 50 ma
should not be used.
Protection diodes m ust be used with inductive loads.
Refer to figure 6-2
Do not parallel outputs for higher drive. This could
result in damage since outputs do not share current
equally.
Interfacing to an opto-module rack
J2 and J3 I/O lines interface to an MPS-8, 16, or 24
position opto module rac k. L ines not going to an opto
module connect to a screw terminal on the MPS-XX
series boards. This feature allows you to connect
switches or other TTL type devices to the digital I/O
lines. The MPS-XX series boards accept G4 series
modules.
Use the O PTO comm and to access and control G4 opto
modules. The LIN E comm and is used to access
individual lines on the STB-26 or MPS-X X rack.
A CM A-26 connects J2 and J3 on the SBS-2300 to the
MPS-XX board. Cable length should be less than 2 feet
for the 8 position rack and 18 inches for the 16 and 24
positions. Excessive cable lengths cause a high voltage
drop and consequently unreliable operation. Be sure to
supply + 5V and ground to the appropriately marked
terminals.
You must configure the 8255 ports for outputs before
using them. Use the following table to determine the
corresponding opto channel for a particular 82C 55 port:
Opto 82C55 Connector Addr.
channels port
M0-M3 Lower C J2 2
M4-M7 Upper C J2 2
M8-M15 A J2 0
M16-M23 B J2 1
M100-M103 Lower C J3 66
M104-M107 Upper C J3 66
M108-M115 A J3 64
M116-M123 B J3 65
"Opto channel" is the position as marked on the MPS-xx
board. The channel number is preceded by a 'M'
character on the MPS board. When connecting J3 to an
opto rack, add 100 to the number on the rack. J3 has a
high current output on port A (channels M8-M15).
Replace U20 with a shunt jumper to operate norm ally.
To turn on an opto module, an output line must be low.
A module is turned off by wr iting a ' 1' to a channel.
The logic at J3 port A, with the high cur rent outputs
installed is just the reverse. A ' 1' at a line causes the
module to turn ON.